Appendix B: Current Monitor Page 259
Figure 188: Current Limit Options
Step 2 Select Upper Limit. The limit checking status
(enabled or disabled) is displayed.
Figure 189: Upper Limit Enable Option
Using the F1=CHANGE OPTION toggle key,
enable/disable the Upper Limit check.
Step 3 Press the Up Arrow and select the F2=LOWER
LIMIT.
Enable the Lower Limit check using the
F1=CHANGE OPTION toggle key.
If a limit check (upper or lower) is disabled, current
checking for that station is not performed and
condemnation and reporting of stations violating that
limit does not occur.
Station Current Limit Setup
The maximum current limit is used to detect shorted solenoid
wiring or a faulty solenoid. A minimum limit value, equal to
50% of the measured station current, is used to detect an open or
broken wire.
UPPER LIMIT CHECK: ENABLED
|F1|=CHANGE OPTION |½|
|F1|=UPPER LIMIT |F2|=LOWER LIMIT
|½|