Appendix B: Current Monitor Page 257
Figure 186: Auto Limits
There are three options:
• Flow Only
• Current Only
• Both Flow and Current
Step 3 Select F2=CURRENT ONLY and enter the station
number. The station number must be between 1 and
48. To measure all stations, enter station number 1,
and then press ENTER.
Note: The maximum number of stations is determined by
the total stations installed in the satellite. The
maximum number (1-xx) will appear on the Station
Number Entry Display.
The following resultant display indicates the station
number, run-time count-down timer, station current
measurement (I) and flow measurement (GPM).
The upper and lower limits of current are
automatically calculated based on the measured
parameters.
The current measuring default time is 5 seconds for
each station. When the count-down clock runs
down, the station number will increment to the next
station and the measurement process is repeated.
With all stations completed, the display returns to
the Auto Limits Options menu. At this point, all
upper and lower percentage values are calculated.
|F1|=FLOW ONLY |F2|=CURRENT ONLY
|F3|=BOTH FLOW AND CURRENT |½|